- Overview
- Product Description
- Product Parameters
- Detailed Information
Basic Info.
Model NO.
CJM2-125 1P
Poles Number
1,2,3,4,1p+N,3p+N
Type
Circuit Breaker
Function
Circuit-Breaker Failure Protection
Certification
ISO9001-2000, CE, CB, TUV
Standard
IEC/En 60947-2
Rated Current
20A,25A,32A,40A,50A,63A,80A,100A,125A
Rated Voltage
AC 230V/400V
Rated Short-Circuit Capacity(Lcn)
10000A
Transport Package
Normal Package
Trademark
CJE
Origin
Wenzhou
HS Code
85362000
Production Capacity
5000000
Product Description
Construction and Feature
1.High short-short capacity 10KA.
2.Designed to protect circuit carrying big current up to 125A.
3.Contact position indication.
4.Used as main switch in household and similar installation.
Standard | IEC/EN 60947-2 |
Pole No | 1P,1P+N, 2P, 3P,3P+N,4P |
Rated voltage | AC 230V/400V |
Rated Current(A) | 20A,25A,32A,40A,50A,63A,80A,100A,125A |
Tripping curve | C, D |
Rated short-circuit capacity(lcn) | 10000A |
Rated service short-circuit capacity(Ics) | 7500A |
Rated frequency | 50/60Hz |
Rated impulse withstand voltage Uimp | 6kV |
Connection terminal | Pillar terminal with clamp |
Electro-mechanical endurance | Ins100=10000:n125=8000 |
Terminali Connection Height | 20mm |
Connection capacity | Flexible conductor 35mm² |
Rigid conductor 50mm² | |
Installation | On symmetrical DIN rail 35mm |
Panel mounting |
Overload Current Protection Characteristics
Test | Tripping Type | Test Current | Initial State | Tripping timeor Non-tripping Time | Provisior |
a | Time-delay | 1.05In | Cold | t≤1h(In≤63A) t≤2h(ln>63A) | No Tripping |
b | Time-delay | 1.30In | After test a | t<1h(In≤63A) t<2h(In>63A) | Tripping |
c | Time-delay | 2In | Cold | 10s<t<60s(In≤63A) 20s<t<120s(In>63A) | Tripping |
d | Instantaneous | 8ln | Cold | t≤0.2s | No Tripping |