- Overview
- Product Description
- Company Profile
Basic Info.
Model NO.
YCM1LE
Frame Current Inm(a)
100,225,400,630
Transport Package
Standard Packaging
Trademark
CNC
Origin
Zhejiang, China
Production Capacity
80000 Set/Sets Per Week
Product Description
CNC 50/60Hz ELCB 4pole ELCB 4p ELCB MCB
YCM1LE series earth leakage circuit breaker (herein after called circuit breaker)is applied for the power distribution network of AC 50Hz,rated current 630A.The circuit breaker can protect people against indirect contact with dangerous electric current and prevent fire disaster caused by insulation fault and single-phase ground fault. It can be used to distribute electric power and protect power equipment against overload and short circuit. The circuit breaker can change the circuit and start motor infrequently. The rated residual operating current and the maximum off-time can be adjusted on-site according to actual situation, the circuit breaker can be customized alarm function and no tripping function.The YCM1LE complies with standard of IEC60947-2
Type | YCM1LE-125 | YCM1LE-250 | YCM1LE-400 | YCM1LE-630 | |||||||||
Frame current Inm(A) | 125 | 250 | 400 | 630 | |||||||||
Rated current In(A) | 10, 16, 20, 25, 32, 40 50, 63, 80, 100, 125 | 100, 125, 140, 160 180, 200, 225, 250 | 225, 315, 350, 400 | 400, 500, 630 | |||||||||
Pole | 2 | 3 | 4 | 2 | 3 | 4 | 3 | 4 | 3 | 4 | |||
Rated insulation voltage Ui(V) | AC800 | ||||||||||||
Rated working voltage Ue(V) | AC400 | ||||||||||||
Rated impulse withstand voltage Uimp(V) | 8000 | ||||||||||||
Arcing-over distance (mm) | 50 | 100 | |||||||||||
Breaking ability level | L | M | L | M | L | M | L | M | |||||
Rated ultimate short-circuit breaking capacity Icu(kA) | 35 | 50 | 35 | 50 | 50 | 65 | 50 | 65 | |||||
Rated working short-circuit breaking capacity Ics(kA) | 22 | 25 | 22 | 25 | 35 | 42 | 35 | 42 | |||||
Rated residual short-circuit breaking capacity | 7.5 | 12.5 | 7.5 | 12.5 | 12.5 | 13.5 | 12.5 | 13.5 | |||||
Rated residual operating current IΔn(mA) | No time-delay type | 30/100/500 100/300/500 | 30/100/500 100/300/500 | 100/300/500 | 300/500/1000 | ||||||||
Time-delay type | 100/300/500 | 100/300/500 | 100/300/500 | 300/500/1000 | |||||||||
Rated residual unoperating current IΔn(mA) | 1/2 IΔn | 1/2 IΔn | 1/2 IΔn | 1/2 IΔn | |||||||||
Operating performance (times) | Power on | 1500 | 1000 | 1000 | 1000 | ||||||||
Power off | 8500 | 7000 | 4000 | 4000 | |||||||||
Total times | 10000 | 8000 | 5000 | 5000 | |||||||||
Residual current protection opreating time | IΔn | 2IΔn | 5IΔn | 10IΔn | |||||||||
Max. breaking time(s) | No time-delay type | 0.2 | 0.1 | 0.04 | 0.04 | ||||||||
Time-delay type | 0.4/1 | 0.4/1 | 0.3/1 | 0.3/1 |