Singi Dz47-63 Performance Heat Resistant University MCB Circuit Breaker

Get reliable protection for your electrical circuits with Singi Dz47-63 Performance Heat Resistant University MCB Circuit Breaker. As a factory, we provide top-quality MCBs for your needs.
Request a Quote

PRODUCTS DETAILS

Basic Info.

Model NO.
DZ47-63
Rated Voltage
220/380VAC
Case Material
PA66
OEM
Avaiable
Keyword
Miniature Circuit Breaker MCB Pdf Viewer
Transport Package
Miniature Circuit Breaker MCB Pdf Viewer Standard
Trademark
SINGI
Origin
Zhejiang, China
Production Capacity
50000 Piece/Pieces Per Day

Product Description

Singi Dz47-63 Performance Heat Resistant University MCB Circuit Breaker

Key Parameters:

· CE/CB/ISO9001/CCC certificates;

· Rated voltage:230/400VAC;

· frequency50/60Hz;

· Rated current:6,10,16,20,25,32,40,50,63A;

· 1/2/3/4poles optional;

· Mechniacal life:20,000times;

· Flame-redardant:PA66 nylon material;

· Protection degree:IP20;

· With over load/short circuit protection;

· Standard:IEC60898;

· Enduring tem.30°C

· Breaking Capacity:4.5KA;

· Lighting/Motor protection optional

 

Application:

DZ47-63 high breaking miniature circuit breaker has the features of structure advanced, performance reliable, breaking capacity high, appearance elegant and its shell and parts are made of material with impact resistance, strong flame-retardant feature.

It is suitable to power system of 50or 60 frequency ,Ue 400V and below, Ui 63A and below.

It is mainly applied at office building, residence, for lighting , power distribution and overload and short circuit protection of equipment. Normally, it also can be used as the not frequent transfer of power system. It conforms to the standards IEC60898and GB10963.1.

 

Technical Parameters:

Rated voltage(V) Poles Rated current(A) Rated short circuit breaking capacity
Test breaking capacity(KA) Power factor
230 1,2 6,10,16,20, 4.5 0.65~0.70
230/400 1,2 25,32, 4.5
400 2,3,4 40 4.5
230 1,2 50,63 4.5 0.75~0.80
230/400 1,2 4.5
400 2,3,4 4.5

 

Remark:

1.mechanical life:20,000 times(off-on).

2.heat resistance: category 2 (temperature 55°C,relative humidity 95%).

3.wiring is terminal with clamp, cable dia.:25mm2.

 

Current Release Character Diagram:

Test current

(A)

Rated current

(A)

Requested time Result Start station Remark
1.13In all t>=1h Don't trip Cool  
1.45In All T<1h trip heat Current ascends the requested value stably in 5s
2.55In In<=32A 1s<t<60s trip Cool Auxiliary switch closed, power is on 
2.55In In>32A 1s<t<120s trip Cool Auxiliary switch closed, power is on 
5In(Cmode) All t>=0.1s Don't trip Cool Auxiliary switch closed, power is on 
10In(Cmode) All T<0.1s  trip Cool Auxiliary switch closed, power is on 
10(Dmode) All t>=0.1s  Don't trip Cool Auxiliary switch closed, power is on 
14In(Dmode) All T<0.1s trip Cool Auxiliary switch closed, power is on 

 

Singi Dz47-63 Performance Heat Resistant University MCB Circuit BreakerSingi Dz47-63 Performance Heat Resistant University MCB Circuit BreakerSingi Dz47-63 Performance Heat Resistant University MCB Circuit BreakerSingi Dz47-63 Performance Heat Resistant University MCB Circuit Breaker

 

Singi Dz47-63 Performance Heat Resistant University MCB Circuit BreakerSingi Dz47-63 Performance Heat Resistant University MCB Circuit BreakerSingi Dz47-63 Performance Heat Resistant University MCB Circuit Breakerrcuit breaker switch 

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours